Reliability
Powered by Experience.
Picture Picture Picture Picture Picture

Polacel CMC cooling towers

The Polacel CMC systems combine a high cooling capacity with low energy consump­tion. The modules are supplied ready to use and they are easy to adjust to cooling require­ments and the available space, whether they are used singly or in series.

The cooling perfor­mance of these cooling towers is optimal and operation is problem free. With a 95%+ saving in water, the efficient CMC systems are the best choice for man and his environ­ment.

Type Wet sur­face (m2) Q min (m3/h) Q max (m3/h) Dimensions Weight Drive type
L (mm) B (mm) H (mm) empty (kg) ope­ra­tio­nal (kg)
CMC1 0,8 6 28 940 940 3.075 270 540 direct
CMC2 1,5 11 53 1.740 940 2.775 310 690 direct
CMC4 2,9 20 102 1.740 1.740 3.055 670 1.780 direct
CMC6 4,3 30 151 2.540 1.740 3.055 900 2.690 direct
                   
CMC9 6,3 44 221 2.540 2.540 4.050 1.260 4.050 geared motor
CMC12 8,3 58 291 3.340 2.540 4.175 1.610 5.410 geared motor
CMC16 10,9 76 382 3.340 3.340 4.575 2.090 7.230 geared motor

 

  • All data is for information only. Please contact Polacel for certified data.
  • All types are available with different air speeds and different fills.
  • Polacel has extensive specifications for all cooling towers listed above.

CMC cooling tower

CMC cooling tower

CMC cooling tower

CMC cooling tower

CMC cooling tower

The effect of coun­ter flow

CMC cooling towers work on the prin­ciple of counter flow. This means that the water flows down while the air is pulled upwards by a fan. As the water flows further through the system, the air it encoun­ters is fresher, in other words cooler and less satu­rated with moisture.

Counter flow cooling towers can approach the wet bulb tempe­rature better compared with cross flow cooling towers.

The secu­rity of quality

Polacel designs and manu­fac­tures cooling towers with long life­times and minimal mainte­nance needs. This is achieved through the materials used - stainless steel combined with glass fibre and plastic - the sound design and the expe­rience of our engi­neers.

'Cheap and cheerful' solu­tions, such as a fan with a V-belt drive or painted panels, are avoided. The result is a cooling tower that is low mainte­nance, energy effi­cient and able to supply constant excellent problem-free perfor­mance.